Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Display a current state operating certificate in the elevator machine room.
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 Provide on-site maintenance documents (MCP).
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.9 Cleaning of Top of Cars Clean the car top.
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Rescue plan is missing. (This item is for notification purposes for future violation in 2022)
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Display current state operating certificate.
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 A record of findings for firefighters' service operation required by 8.6.11.1 with identification of the person(s) that performed the operation shall be kept on site.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts The standby power selector switch and light shall be removed or marked "for future use" - the building is not equipped with emergency power for the elevators.
A17.1-1996 : Elevators 1.18 - Restricted opening of car or hoistway doors 1001.2(a)(18) x Make car door restrictor operational. 6/6/2019
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Fire service operation shall be tested as required.
A17.1-1996 : Elevators 1.17 - Standby power operation 1001.2(a)(17) x Emergency power shall be tested. 9/30/2021
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Need to simulate the fire alarm initiating devices for phase 1 recall. 9/30/2021
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Category 5 testing shall be completed. The following testing items remain: Counterweight buffer shall be tested at contract speed, 125% brake test, car safeties shall be set at contract speed with full load, and car buffer shall be tested with full load at contract speed. 9/13/2022
A17.1-1996 : Elevators 1.6 - Car emergency signal 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency phone shall be tested and shall operate with and without main power. 9/19/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Fire service shall be tested to complete the annual inspection. 9/19/2023