A17.1-1996 : Elevators
|
1.17 - Standby power operation
|
1001.2(a)(17)
|
x
|
|
Emergency power shall be tested.
|
9/8/2021
|
|
A17.1-1996 : Elevators
|
1.18 - Restricted opening of car or hoistway doors
|
1001.2(a)(18)
|
x
|
|
Make car door restrictor operational.
|
6/6/2019
|
|
A17.1-1996 : Elevators
|
3.20 - Governor rope
|
1001.2(c)(26)
|
x
|
|
The governor rope tail sheave is nearing the limits of it's travel. The governor rope shall be shortened.
|
9/8/2021
|
|
A17.1-1996 : Elevators
|
2.3 - Lighting and receptacles
|
101.5a Lighting
|
|
|
Lighting in machine room shall be not less than 10fc at floor level. Recommend adding light fixture over controller as personnel are having a hard time seeing equipment.
|
|
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Two-way communication device is not functioning and needs repair.
|
|
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
|
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Display a current state operating certificate in the elevator machine room.
|
|
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Display current state operating certificate.
|
|
|
A17.1-1996 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022)
|
|
|
A17.1-1996 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
Provide on-site maintenance documents (MCP).
|
|
|
A17.1-1996 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
A maintenance control program shall be provided in machine room.
|
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Fire service shall be tested to complete the annual inspection.
|
9/19/2023
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Fire service operation shall be tested to complete the annual inspection.
|
9/27/2021
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Need to simulate the fire alarm initiating devices for phase 1 recall.
|
9/8/2021
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
The in car emergency telephone shall be tested and shall be code compliant.
|
9/19/2023
|
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.6.11.1 Monthly Test and Log
|
|
|
A record of findings for firefighters' service operation required by 8.6.11.1 with identification of the person(s) that performed the operation shall be kept on site.
|
|