Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)12 (Door open zones) x Car door restrictor battery back-up does not work. 4/17/2020
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)3 Cut off car top channel blocking emergency exit. 7/23/2021
MO Minimum : Elevators (F) - Electrical Switches (F)9 Disconnecting means is hard to get to causing a safety hazard. Mechanic has to touch metal to shut disconnect
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements Fire extinguisher needs to be serviced. 2.7.1 11/7/2018
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) Pit light does not work
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing OSV is not sealed and must have a category 5 weight test performed within 90 days or less
conversion conversion conversion - reinspect x Cut off channel on Car top blocking escape hatch. 16" clear opening required. 9/12/2018
conversion conversion conversion - reinspect x Replace roustabout fitting on supply line near pump unit. 9/12/2018