MO Minimum : Elevators
|
(M) - Car Safeties and Speed Governors
|
(M)1
|
x
|
x
|
Test car safeties with rated load.
|
12/17/2019
|
MO Minimum : Elevators
|
(D) - Brakes
|
(D)1
|
x
|
x
|
Test brake with 125% of rated load. Reinspect within 30 days.
|
12/17/2019
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
Written maintenance control program shall be kept on site for each elevator.
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A copy of the current state operating certificate shall be displayed in the machine room
|
6/29/2023
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Test incomplete, need to perform the following test to complete inspection: Pull out and pull through force of governor, test tripping speeds of governor overspeed switch and governor jaws, unintended movement test with 125% of rated load, traction drive machine brake test with 125% of rated load & test car safeties with rated load at rated speed. Re-inspection required
|
1/20/2025
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Elevator cab phone does not work. Re-inspection required
|
1/20/2025
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A copy of the current operating certificate shall be displayed in the elevator machine room
|
|