Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records Written maintenance control program shall be kept on site for each elevator.
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A copy of the current state operating certificate shall be displayed in the machine room 6/29/2023
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A copy of the current operating certificate shall be displayed in the elevator machine room
MO Minimum : Elevators (M) - Car Safeties and Speed Governors (M)1 x x Test car safeties with rated load. 12/17/2019
MO Minimum : Elevators (D) - Brakes (D)1 x x Test brake with 125% of rated load. Reinspect within 30 days. 12/17/2019
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Test incomplete, need to perform the following test to complete inspection: Pull out and pull through force of governor, test tripping speeds of governor overspeed switch and governor jaws, unintended movement test with 125% of rated load, traction drive machine brake test with 125% of rated load & test car safeties with rated load at rated speed. Re-inspection required 1/20/2025
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Elevator cab phone does not work. Re-inspection required 1/20/2025