Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts Counterweight guide rollers are deteriorated and causes unsafe conditions. Re-inspection required
MO Minimum : Elevators (S) - Fire Service (S)1 x x During fire service phase II, the light ray is not overridden. RED TAGGED, Re-inspection required 12/19/2024
A17.1-2016 : Elevators 3.28 - Counterweight and counterweight buffer 8.11.2.1.3(m) x Multiple guide rollers have deteriorated to the point of an unsafe condition to operate the elevator is present. The deteriorated guide rollers shall be replaced and reinspection shall be performed before the elevator can be returned to service. 5/5/2021
conversion conversion n/a Replace 2 counterweight rollers - top left side 2/20/2019
conversion conversion n/a Replace box cover - top of third floor 2/20/2019
MO Minimum : Elevators (J) - Counterweights (J)2 Replace counterweight roller guides.
conversion conversion n/a shorten hoist cables 2/20/2019
MO Minimum : Elevators (S) - Fire Service (S)1 x x The fireman's emergency service phase I and II operations was tested and the following deficiency was noted: Phase I did not initiate when the fireman's emergency service key was turned to the “ON” position. The fireman’s service shall be repaired and reinspection shall be performed before the elevator can be returned to service. 5/5/2021