Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 3.12 - Pipes, wiring, and ducts 8.11.2.1.3(r) A receptacle box is missing its cover plate on top of the car exposing electrical connections. The cover plate shall be reinstalled to limit accidental contact by maintenance and emergency personnel. 3/26/2024
conversion conversion conversion - reinspect x Adjust car door close pressure to under 30lb. 11/16/2018
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts x Bottom c/w roller guides bad, replace. 1/7/2025
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)7 x Car door closing force is way above 30 lbs and shall be adjusted to 30 lbs or below. Re-inspection required 3/26/2024
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)7 x Car door force exceeds code, adjust as needed. 3/26/2024
MO Minimum : Elevators (A) - Hoistways (A)16 x Car top electric j/b missing cover. 1/7/2025
MO Minimum : Elevators (A) - Hoistways (A)16 Car top electric junction box missing cover.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.9 Cleaning of Top of Cars Clean the car top.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts Counterweight guide rollers are deteriorated and causes unsafe condition. Re-inspection required 3/26/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts x Counterweight rollers are deteriorating and shall be replaced. Re-inspection required 3/26/2024
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)7 x Door force exceeds code. 1/7/2025
conversion conversion n/a Handi-box cover on cart top is missing 2/20/2019
conversion conversion n/a No fire extinguisher in machine room 2/20/2019
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x x Phase I recall not working, car removed from service. 3/26/2024
A17.1-2016 : Elevators 4.12 - Standby power selection switch 8.6.4.19.7 (Re-Inspection) x Provide testing of the elevator emergency power selector switch (lobby). 3/26/2024
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x Provide testing of the elevator on emergency power. 3/26/2024
conversion conversion n/a Replace or reinforce catwalk in pit 2/20/2019
A17.1-2016 : Elevators 3.28 - Counterweight and counterweight buffer 8.11.2.1.3(m) The bottom guide rollers on the counterweight are cracked and shall be replaced. 3/26/2024
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)7 The elevator car door closing force is over the maximum allowable force of 30lbs. Readjust door closing force to be less than 30lbs. Reinspection required. 3/26/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts Top and bottom counterweight roller guides worn, replace as needed.