MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
|
|
Need "In Case of Fire" signs by each Hall Call button. I am aware of the signage on the walls that has the info in it, but it is not to code.
|
9/24/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.4.11 Runby (Re-Inspection)
|
x
|
|
Hoist ropes need to shortened to provide sufficient counterweight to buffer clearance. Currently does not meet 6" minimum standard.
|
11/2/2022
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)5 (Machine Room Lighting)
|
|
|
Lighting in Elevator equipment room shall be no less 10FC measured at floor for all machinery in equipment room
|
3/18/2020
|