Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts Covers missing from rear gate limit switches
MO Minimum : Elevators (M) - Car Safeties and Speed Governors (M)4 x x Left lower Safety mechanism/guide shoe is bent away from guide rail. Must be replaced and tested per A17.1 Sec 8.6 12/4/2019
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) Lights in machine room are not working.
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) Ligthing in Elevator equipment room shall not be less that 10 FC measured at the floor by each piece of equipment.