Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) Yes No Elevator phone is not working. Re-inspection required 8/4/2025
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) Yes No On Phase II operation, call cancel function not working correctly. Re-inspection required 8/4/2025
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing (Re-Inspect) Yes No OSV is not sealed. Re-inspection required 8/4/2025
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Provide existing battery backup lowering unit to work correctly. 11/28/2023
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) Yes No Phone in car has power, needs programming. 11/28/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing Yes No OSV in pit is not sealed, provide testing. 11/28/2023
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Post current operating certficate in machine room. 10/20/2023
A17.1-2016 : Elevators 5.15.2 Unsealed Overspeed Valve 8.6.5.16.5 (Re-Inspect) Yes No Unsealed 7/22/2022
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Emergency phone does not work. 1/24/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) Yes No Emergency alarm in car is not working. Re-inspection required
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) Yes No Emergency light in car does not work. Re-inspection required
MO Minimum : Elevators (I) - Pits (I)1 No No Observed sump pump not working correctly, repair/replace as needed.
MO Minimum : Elevators (I) - Pits (I)1 No No Provide means to prevent accumulation of groundwater in the pit.
MO Minimum : Elevators (I) - Pits (I)1 No No Need to remove water from pit
MO Minimum : Elevators (I) - Pits (I)1 No No Need to provide working sump pump on pit
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) No No Provide for pit light to work
MO Minimum : Elevators (I) - Pits (I)8 No No Sump hole filled with oil, remove. Determine if sump pump works, if not replace.
A17.1-1996 : Elevators 1.17 - Standby power operation 1002.2g (Standby Power Operation) Yes No Emergency battery lowering device is not working, needs repaired. Re-inspection required
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1 No No Need to provide means to prevent ground water from entering pit
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 211.3a(8) Visual and audible signal Yes No Indicator for fire service phase I in car shall work, needs repaired. Re-inspection required
A17.1-1996 : Elevators 2.10 - Numbering of elevators, machines, and disconnect switches 211.9 No No Existing inside Hoistway door numbering does not match door buck numbering. Confirm COP,door buck, and Hoistway doors all numbered same.
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Expired
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A copy of the current state operating certificate shall be displayed in the machine room
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A copy of the current state operating certificate shall be displayed in the machine room
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) Yes No On phase I operation, call cancel function is not working correctly. Re-inspection required
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.2(a) On-Site Documentation (Up-to-Date Wiring Diagrams) No No Provide up-to-date wiring diagrams & maintenance records in maintenance control program
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) No No None