MO Minimum : Elevators
|
(I) - Pits
|
(I)8
|
|
|
Sump hole filled with oil, remove. Determine if sump pump works, if not replace.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4.1(a) On-Site Maintenance Records (MCP Records)
|
|
|
None
|
|
A17.1-1996 : Elevators
|
2.10 - Numbering of elevators, machines, and disconnect switches
|
211.9
|
|
|
Existing inside Hoistway door numbering does not match door buck numbering. Confirm COP,door buck, and Hoistway doors all numbered same.
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Observed sump pump not working correctly, repair/replace as needed.
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Provide means to prevent accumulation of groundwater in the pit.
|
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Post current operating certficate in machine room.
|
10/20/2023
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Expired
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Need to remove water from pit
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Need to provide working sump pump on pit
|
|
A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
106.1
|
|
|
Need to provide means to prevent ground water from entering pit
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A copy of the current state operating certificate shall be displayed in the machine room
|
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Elevator phone is not working. Re-inspection required
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.6.5.16.5 Over Speed Valve Testing (Re-Inspect)
|
x
|
|
OSV is not sealed. Re-inspection required
|
|
A17.1-2016 : Elevators
|
5.15.2 Unsealed Overspeed Valve
|
8.6.5.16.5 (Re-Inspect)
|
x
|
|
Unsealed
|
7/22/2022
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone does not work.
|
1/24/2022
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.6.5.16.5 Over Speed Valve Testing
|
x
|
|
OSV in pit is not sealed, provide testing.
|
11/28/2023
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Phone in car has power, needs programming.
|
11/28/2023
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Provide existing battery backup lowering unit to work correctly.
|
11/28/2023
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection)
|
x
|
|
On Phase II operation, call cancel function not working correctly. Re-inspection required
|
|