Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Provide existing battery backup lowering unit to work correctly. 11/28/2023
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Elevator phone is not working. Re-inspection required
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Phone in car has power, needs programming. 11/28/2023
MO Minimum : Elevators (I) - Pits (I)1 Need to remove water from pit
MO Minimum : Elevators (I) - Pits (I)1 Need to provide working sump pump on pit
MO Minimum : Elevators (I) - Pits (I)1 Observed sump pump not working correctly, repair/replace as needed.
MO Minimum : Elevators (I) - Pits (I)1 Provide means to prevent accumulation of groundwater in the pit.
MO Minimum : Elevators (I) - Pits (I)8 Sump hole filled with oil, remove. Determine if sump pump works, if not replace.
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency phone does not work. 1/24/2022
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1 Need to provide means to prevent ground water from entering pit
A17.1-1996 : Elevators 2.10 - Numbering of elevators, machines, and disconnect switches 211.9 Existing inside Hoistway door numbering does not match door buck numbering. Confirm COP,door buck, and Hoistway doors all numbered same.
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current operating certficate in machine room. 10/20/2023
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Expired
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A copy of the current state operating certificate shall be displayed in the machine room
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x On Phase II operation, call cancel function not working correctly. Re-inspection required
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) None
A17.1-2016 : Elevators 5.15.2 Unsealed Overspeed Valve 8.6.5.16.5 (Re-Inspect) x Unsealed 7/22/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing x OSV in pit is not sealed, provide testing. 11/28/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing (Re-Inspect) x OSV is not sealed. Re-inspection required