Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) Yes No Phone not working--building vacant / being sold 8/24/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements Yes No Violation of A17.1 Rule 102.2(c)(3) The means shall be provided to automatically disconnect the main line power supply to the affected elevator upon or prior to the application of water. 8/1/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements Yes No Violation A17.1 Rule 102.2(c)(3) the means to automatically disconnect the main line power supply to the affected elevator prior to the application of water, with a Shunt trip Device and Heat Device as well as a Smoke Device to send elevator to the main floor egress. 8/29/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts No No Pickup rollers need to be changed 10/12/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records No No Need maint records. KONE NEEDS TO SUPPLY 10/12/2020
MO Minimum : Elevators (H) - Machine Rooms (H)2 No No Door needs to be self locking/closing 10/12/2020
MO Minimum : Elevators (H) - Machine Rooms (H)2 Yes No Violation of A17.1 Rule 102.2(c)(1) Building Sprinkler Lines have been brought thru the Elevator Machine Room with 3 penetration points.. Lines must be removed. points 8/1/2024
MO Minimum : Elevators (I) - Pits (I)1 No No Elevator pit must be keep dry and clean. Remove the oil from pit can overflow.
MO Minimum : Elevators (S) - Fire Service 211.7 Firefighters Operations/Signage No No Need Phase I and II operating instructions 10/12/2020