MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Elevator pit must be keep dry and clean. Remove the oil from pit can overflow.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 Maintenance, Repair and Replacements
|
x
|
|
Violation A17.1 Rule 102.2(c)(3) the means to automatically disconnect the main line power supply to the affected elevator prior to the application of water, with a Shunt trip Device and Heat Device as well as a Smoke Device to send elevator to the main floor egress.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.2.1 Repair Parts
|
|
|
Pickup rollers need to be changed
|
10/12/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
Need maint records. KONE NEEDS TO SUPPLY
|
10/12/2020
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
Door needs to be self locking/closing
|
10/12/2020
|
MO Minimum : Elevators
|
(S) - Fire Service
|
211.7 Firefighters Operations/Signage
|
|
|
Need Phase I and II operating instructions
|
10/12/2020
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Phone not working--building vacant / being sold
|
8/24/2023
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
x
|
|
Violation of A17.1 Rule 102.2(c)(1) Building Sprinkler Lines have been brought thru the Elevator Machine Room with 3 penetration points.. Lines must be removed. points
|
8/1/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 Maintenance, Repair and Replacements
|
x
|
|
Violation of A17.1 Rule 102.2(c)(3) The means shall be provided to automatically disconnect the main line power supply to the affected elevator upon or prior to the application of water.
|
8/1/2024
|