MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.4.7 Cleaning of Hoistway and Pit
|
|
|
The elevator pit has a noticeable amount of debris and shall be cleaned.
|
3/26/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6 General Maintenance Methods
|
|
|
The emergency rescue battery in the controller has not been changed since 2019. The manufacture’s recommendation for replacement is 3 years. Replacement of the battery before the elevator shuts down due to battery being depleted is required.
|
3/26/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.17 - Standby power operation
|
2.27.2
|
x
|
|
Perform the required Cat 1 testing of the emergency generator
|
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
1004.2(a)(6) (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone not working.
|
3/2/2020
|
A17.1-1996 : Elevators
|
2.7 - Fire Extinguisher
|
1206.1h
|
|
|
No fire extinguisher in machine room.
|
5/26/2020
|
A17.1-1996 : Elevators
|
3.23 - Suspension rope
|
1001.2(c)(29)
|
x
|
|
Clear faults on rope monitor after repairing any issues with CSB. 8.6.4.19.13
|
11/3/2022
|
A17.1-1996 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
1002.2f
|
x
|
|
The fireman's emergency service phase I and II operations was tested and the following deficiency was noted: The “call cancel” button is not labeled inside the car and shall be labeled correctly.
|
2/13/2024
|
conversion
|
conversion
|
n/a
|
|
|
Travel cable cracking in cover at several floors 2,3 & 4, repair and wrap.
|
5/26/2020
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Display updated certificate in machine room.
|
5/26/2020
|