Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Display updated certificate in machine room. 5/26/2020
A17.1-1996 : Elevators 1.6 - Car emergency signal 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency phone not working. 3/2/2020
A17.1-1996 : Elevators 2.7 - Fire Extinguisher 1206.1h No fire extinguisher in machine room. 5/26/2020
A17.1-2016 : Elevators 1.17 - Standby power operation 2.27.2 x Perform the required Cat 1 testing of the emergency generator 2/11/2025
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current State Elevator Certificate.
A17.1-1996 : Elevators 1.2 - Stop switches 1001.2(a)(2) Repair in car stop switch. 5/26/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods The emergency rescue battery in the controller has not been changed since 2019. The manufacture’s recommendation for replacement is 3 years. Replacement of the battery before the elevator shuts down due to battery being depleted is required. 3/26/2024
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1002.2f x The fireman's emergency service phase I and II operations was tested and the following deficiency was noted: The “call cancel” button is not labeled inside the car and shall be labeled correctly. 2/13/2024