Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Provide existing battery backup lowering unit to work correctly. 8/4/2023
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A copy of the current state operating certificate shall be displayed in the machine room
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates No No Need to replace missing elevator capacity signage in elevator cab
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Post current State Elevator Certificate. 3/14/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates No No Replace missing elevator capacity signage in elevator cab
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates No No Replace missing in-car capacity plate.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods No No The battery back–up lowering device was tested and did not operate as designed, the elevator failed to return to a lower floor and open its doors. Repair the device to operate as it is designed. 3/14/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing No No This elevator is equipped with an overspeed valve. A category 5 test shall be performed on the overspeed valve on or before the next annual inspection.
conversion conversion n/a No No Fire extinguisher needs to be serviced 11/20/2019
conversion conversion n/a No No Front door torque needs to be adjusted below 30 pounds 11/20/2019
A17.1-1996 : Elevators 3.4 - Top-of-car Clearance, Refuge Space, & Standard Railing 1206.2(c) No No Securely fasten car top handrail at all points. 11/20/2019
A17.1-1996 : Elevators 3.8 - Top emergency exit 204.1e No No Top emergency exit shall be properly secured. The latches are broken.