Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting NEC 620 When shutting off C/B for car lights to check emergency battery, shunt trip breaker shuts down elevator when you turn the C/B for car lights back on. Whoever wired up Shunt trip did not do it correctly. It must be corrected. 2nd Request. 9/30/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates Need In Case of Fire signs by each hall call button 12/21/1202
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x Phone is not working. Line to controller is good. 8/31/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency phone not working 6/30/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates In case of fire use stairs signage needed 12/21/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency phone not working. Phone? 7/17/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency phone not working. Line? 4/2/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency phone not working. Phone line good. Needs programming from bldg IT department 7/10/2024
MO Minimum : Elevators (H) - Machine Rooms (H)2 Machine room door must be self-locking 12/21/2023
MO Minimum : Elevators (H) - Machine Rooms (H)2 Machine room door must be self-locking 12/21/2023
MO Minimum : Elevators (H) - Machine Rooms (H)2 Machine room door must be self-locking 12/21/2023
conversion conversion n/a When shutting off C/B for car lights to check emergency battery shunt trip breaker shuts down elevator when you turn the C/B for car lights back on. Whoever wired in shunt tip did not do it correctly in must be corrected. 9/30/2020