Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
conversion conversion conversion - reinspect Yes No Car stop switch is not bypassed on Phase 1 Fire Recall. 10/2/2018
MO Minimum : Elevators (S) - Fire Service (S)1 Yes No Door open button does not work on Phase 1 fire recall. 12/11/2018
MO Minimum : Elevators (S) - Fire Service (S)1 Yes No Constant pressure on the door close button on Phase 2 fire service does not work. 12/11/2018
MO Minimum : Elevators (S) - Fire Service (S)1 Yes No The hold feature on Phase 2 fire service does not work. 12/11/2018
MO Minimum : Elevators (S) - Fire Service (S)1 Yes No Call cancel feature does not work. 12/11/2018