MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection)
|
Yes
|
No
|
Restrictor is broken and shall be repaired.
|
10/16/2025
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection)
|
Yes
|
No
|
CAR DOOR SHALL BE RESTRICTED FROM OPENING (more than 4") WHEN OUTSIDE DOOR ZONE.
|
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
Yes
|
No
|
Emergency communications/phone not working reinspection item 30 day maximum
|
3/6/2024
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
Yes
|
No
|
Building currently changing billing 30 day extension has been granted from date of this report
|
4/25/2024
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 Maintenance, Repair and Replacements
|
No
|
No
|
A standard railing conforming to 2.10.2 shall be provided on the outside perimeter of the car top on all sides where horizontal clearance exceeds 12" . Hoistway is an open hoistway with rear of cab open to the atrium. Install appropriate standard railing or file for a variance with the State Board
|
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 Maintenance, Repair and Replacements
|
No
|
No
|
Top emergency exit shall be properly secured
|
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 Maintenance, Repair and Replacements
|
No
|
No
|
Adjust upthrust roller bearings for proper clearance to door hanger track and lower door to door gap.(all floors)
|
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 Maintenance, Repair and Replacements
|
No
|
No
|
Load Cell mounted to end of hoist ropes (car side) striking metal plate at the top of hoistway.
|
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 Maintenance, Repair and Replacements
|
No
|
No
|
Travel cable insulation damaged(seen from 1st landing door with car at 2nd landing.) Shall be properly repaired or replaced
|
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.16 - Rated load, platform area, and data plate
|
2.16.3.1 Capacity Plates
|
No
|
No
|
Provide the correct capacity data plate on the hoist machine. - Self Certification violation from 2019
|
10/14/2021
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
No
|
No
|
Post current state certificate in machine room
|
3/29/2024
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
No
|
No
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
10/16/2025
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.15 - sign and operating device symbols
|
8.11.2.1.1(o)
|
No
|
No
|
Provide braille/tactile plates on all door jambs. - Self Certification violation from 2019
|
10/14/2021
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.16 - Rated load, platform area, and data plate
|
8.11.2.1.1(p)
|
No
|
No
|
Provide the correct capacity data plate on the hoist machine.
|
10/14/2021
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.17 - Drive machine brake
|
8.11.2.1.2(o)
|
Yes
|
Yes
|
The emergency brake shall operate properly. - Unit Red Tagged.
|
5/27/2020
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
4.2 - Hoistway doors
|
8.11.2.1.4(b)
|
Yes
|
No
|
Provide braille/tactile plates on all door jambs.
|
5/6/2020
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
No
|
No
|
Machine Room shall have proper Fire Extinguisher and shall have current monthly/annual test tag.
|
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
No
|
No
|
Attach "DANGER LOW CLEARANCE" on the crosshead for top of car to Top of Hoistway ceiling clearance.
|
|
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.6.11.1 Monthly Test and Log
|
No
|
No
|
MCP - Fire Service must be tested and properly documented monthly on Log Sheet. Almost all are blank.
|
|