Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Elevators that are equipped to operate on Emergency Power shall be tested operating on Em Power, Annually.
MO Minimum : Elevators (A) - Hoistways (A)1 No No Hoistway door(s) have missing or loose guides on 1st,2nd, and 5th floors. Repair/replace as needed.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) Yes No Restrictor is broken and shall be repaired. 10/16/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) Yes No ALARM BELL SHALL WORK WITH LOSS OF MAIN 120v POWER
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) Yes No Emergency communications/phone not working reinspection item 30 day maximum 3/6/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) Yes No building currently changing billing 30 day extension has been granted from date of this report 4/25/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) Yes No EMERGENCY LIGHTING SHALL WORK WITH LOSS OF MAIN 120v POWER
MO Minimum : Elevators (H) - Machine Rooms (H)8 No No 2 electrical boxes in machine room need to have wiring inside box and covers installed.
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 10/16/2025
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Post current state certificate in machine room 2/2/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers No No Machine Room shall have proper Fire Extinguisher and shall have current monthly/annual test tag. No extinguisher present
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log No No MCP - Fire Service must be tested and properly documented monthly on Log Sheet. Almost all are blank.