MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
Yes
|
No
|
Elevators that are equipped to operate on Emergency Power shall be tested operating on Em Power, Annually.
|
|
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)1
|
No
|
No
|
Hoistway door(s) have missing or loose guides on 1st,2nd, and 5th floors. Repair/replace as needed.
|
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection)
|
Yes
|
No
|
Restrictor is broken and shall be repaired.
|
10/16/2025
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
Yes
|
No
|
ALARM BELL SHALL WORK WITH LOSS OF MAIN 120v POWER
|
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
Yes
|
No
|
Emergency communications/phone not working reinspection item 30 day maximum
|
3/6/2024
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
Yes
|
No
|
building currently changing billing 30 day extension has been granted from date of this report
|
4/25/2024
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection)
|
Yes
|
No
|
EMERGENCY LIGHTING SHALL WORK WITH LOSS OF MAIN 120v POWER
|
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)8
|
No
|
No
|
2 electrical boxes in machine room need to have wiring inside box and covers installed.
|
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
No
|
No
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
10/16/2025
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
No
|
No
|
Post current state certificate in machine room
|
2/2/2024
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
No
|
No
|
Machine Room shall have proper Fire Extinguisher and shall have current monthly/annual test tag. No extinguisher present
|
|
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.6.11.1 Monthly Test and Log
|
No
|
No
|
MCP - Fire Service must be tested and properly documented monthly on Log Sheet. Almost all are blank.
|
|