Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 1.6 - Car emergency signal 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No The elevator ADA telephone inside the elevator is not working properly. Two-way communication could not be established. Repair/replace this phone for proper operation and passenger safety. Reinspection required.
A17.1-1996 : Elevators 2.3 - Lighting and receptacles 101.5a Lighting No No Machine room lighting illumination is less than 10 fc. Replace lights that are out 2/15/2024
A17.1-1996 : Elevators 2.37 Pressure switch 306.14 Pressure switch Yes No Install pressure switch on valve. 5/17/2021