Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 2.3 - Lighting and receptacles 101.5a Lighting Machine room lighting illumination is less than 10 fc. Replace lights that are out 2/15/2024
A17.1-1996 : Elevators 2.37 Pressure switch 306.14 Pressure switch x Install pressure switch on valve. 5/17/2021