Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13 - Door systems 12th floor hoistway door shall be adjusted to self-close.
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Fire service phase 1 and 2 and emergency generator power operation need to be tested t complete 5 year inspection
MO Minimum : Elevators (M) - Car Safeties and Speed Governors (M)1 x x Car slide does not meet minimum requirements for rated speed. Red tagged elevator. 7/14/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Incomplete inspection. Need to conduct buffer test. 7/14/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x The testing has not been completed on the elevator at this time due to the following items: 1 - Counterweight buffer has not been tested. Unable to complete due to construction being performed in the hoistway. 2 - The brake has not been tested with a load of 125%. Unable to complete due to door operator motor being repaired. 1/17/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x The emergency car lighting is not operational, likely indicating that the back-up power device (battery) has failed. The fixture shall be repaired to operate. Reinspection required. 5/9/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x When testing the audible signaling device (alarm bell) with the 110V disconnect in the machine room in the “off” position, the device failed to sound, indicating that the back-up power device (battery) has failed. Repair for proper operation. Reinspection required. 5/9/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x The Category 5 testing has not been completed on the elevator at this time due to the following items: 1 - Counterweight buffer has not been tested. 2 - The brake has not been tested with a load of 125%. 3 - Fireman’s Service testing has not been performed. 4 - Emergency power testing has not been performed. 5/9/2023