MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.13 - Door systems
|
|
|
12th floor hoistway door shall be adjusted to self-close.
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Fire service phase 1 and 2 and emergency generator power operation need to be tested t complete 5 year inspection
|
|
MO Minimum : Elevators
|
(M) - Car Safeties and Speed Governors
|
(M)1
|
x
|
x
|
Car slide does not meet minimum requirements for rated speed. Red tagged elevator.
|
7/14/2022
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Incomplete inspection. Need to conduct buffer test.
|
7/14/2022
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
The testing has not been completed on the elevator at this time due to the following items: 1 - Counterweight buffer has not been tested. Unable to complete due to construction being performed in the hoistway. 2 - The brake has not been tested with a load of 125%. Unable to complete due to door operator motor being repaired.
|
1/17/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection)
|
x
|
|
The emergency car lighting is not operational, likely indicating that the back-up power device (battery) has failed. The fixture shall be repaired to operate. Reinspection required.
|
5/9/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection)
|
x
|
|
When testing the audible signaling device (alarm bell) with the 110V disconnect in the machine room in the “off” position, the device failed to sound, indicating that the back-up power device (battery) has failed. Repair for proper operation. Reinspection required.
|
5/9/2023
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
The Category 5 testing has not been completed on the elevator at this time due to the following items: 1 - Counterweight buffer has not been tested. 2 - The brake has not been tested with a load of 125%. 3 - Fireman’s Service testing has not been performed. 4 - Emergency power testing has not been performed.
|
5/9/2023
|