Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (S) - Fire Service 211.7 Firefighters Operations/Signage Ph2 Call Cancel button shall be labeled, Ph2 Bezel shall be readable 9/22/2025
MO Minimum : Elevators (S) - Fire Service 211.7 Firefighters Operations/Signage Phase 2 bezel shall be readable
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods Safety Rod Bushings shall be replaced (deteriorated)
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.2 Replacement of Suspension Means (Re-Inspection) x Hoist ropes are undersized and have multiple broken strands across several ropes
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.2 Replacement of Suspension Means (Re-Inspection) x x Hoist ropes are undersized and have multiple broken strands across several ropes 9/22/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods x Safety Rod Bushing shall be replaced (deteriorated) 9/22/2025
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Emergency Power needs to be tested 9/22/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency phone does not work properly. 7/21/2021
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Test incomplete, need to test 125% brake test. Re-inspection required 1/17/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Test incomplete, need to complete full load buffer test for car & counterweight. Re-inspection required 1/17/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Test incomplete, need to test full load safety set. Re-inspection required 1/17/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Test incomplete, need to test spin governor. Re-inspection required 1/17/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x The testing has not been completed on the elevator at this time. The category 5 test was never completed and only a machine room inspection could be performed. The weight test shall be performed, safeties set, buffers compressed, door pressure, hoistway inspection, fireman’s emergency service, in car inspection, and emergency power operation tested before the inspection is completed. 8/21/2025