Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A copy of the current operating certificate shall be displayed in the machine room 9/22/2025
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Current operating certificate shall be displayed in the machine room 9/22/2025
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Current Operating Certificate shall be displayed in the machine room 11/18/2025
A17.1-2016 : Elevators 3.14 - Hoistway clearances 2.4 No No Seismic strengthening of the elevator hoistway has been performed. This has resulted in a number of issues listed. 1- No alteration permit has been applied for. 2-The elevator car has struck the seismic bolts that have been added to the hoistway. Clearances shall be checked. 3-Elevator car door header has been damaged by striking seismic bolts in the hoistway. 4-The seismic contractor (Paric) shall finish the work in the hoistway and certify its completion before the elevator can be returned to service. Numerous nuts were observed that were not properly secured and could potential cause damage to the elevator and the occupants inside. 9/22/2025
A17.1-2016 : Elevators 3.14 - Hoistway clearances 2.4 No No Seismic strengthening of the elevator hoistway has been performed. This has resulted in a number of issues listed. 1- No alteration permit has been applied for. 2-The elevator car has struck the seismic bolts that have been added to the hoistway. Clearances shall be checked. 3-Elevator car door header has been damaged by striking seismic bolts in the hoistway. 4-The seismic contractor (Paric) shall finish the work in the hoistway and certify its completion before the elevator can be returned to service. Numerous nuts were observed that were not properly secured and could potential cause damage to the elevator and the occupants inside. 9/22/2025
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Counterweights need to be tested. Re-inspection required 1/18/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Has not completed the Category 5 Inspection for 2022. The following issues are unresolved: 1 - Counterweight buffer has not been tested. Unable to complete due to seismic construction. 2 - Car buffer has not been tested. Unable to complete due to seismic construction. 3 - The governor rope has been damaged and shall be replaced. 4 - Fireman’s emergency service phase I and II have not been tested. Unable to reinspect due to being out of service for repair. 5/9/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Fire service phase 1 and 2 and emergency generator power operation still needs to be tested to complete 5 year inspection 12/4/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Test elevator for operation on emergency power. Re-inspection required 8/21/2025
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Emergency Power needs to be tested - Test not completed 9/20/2025
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) Yes No Fire service needs to be tested. Re-inspection required 1/18/2023
MO Minimum : Elevators (S) - Fire Service 211.7 Firefighters Operations/Signage No No FEO Phase 2 Bezel shall be labeled. 9/22/2025
MO Minimum : Elevators (S) - Fire Service 211.7 Firefighters Operations/Signage No No Call Cancel button shall be labeled 11/18/2025
MO Minimum : Elevators (S) - Fire Service 211.7 Firefighters Operations/Signage No No FEO Phase 2 Bezel shall be labeled. 11/18/2025
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)12 (Re- Inspection) Yes No Governor rope must be replaced. Re-inspection required 1/18/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts No No Hoist rope shackle spring is broken. Replace same 9/22/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts No No Down final limit switch roller is damaged and needs replacing 9/22/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts No No Suspension rope shackle spring is broken in machine room, needs to be replaced 9/22/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) Yes No Emergency light not working. Re-inspection required 1/18/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements No No Two shackle springs are broken, need to be replaced 9/22/2025
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)7 No No Unable to test door pressure due damage incurred from striking the seismic bolts in the hoistway. 9/22/2025
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) Yes No Elevator cab phone is not working on battery backup, needs repaired. Re-inspection required 8/21/2025
MO Minimum : Elevators (A) - Hoistways (A)13 Yes No Seismic strengthening of the elevator hoistway has been performed. No alteration permit was obtained. Numerous nuts on west wall are loose and could potential cause damage to the elevator/occupants. 9/20/2025
MO Minimum : Elevators (A) - Hoistways (A)13 No No Numerous nuts on west wall are loose and could potential cause damage to the elevator/occupants. 11/18/2025