Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Phone in elevator cab does not work on battery backup or normal power, needs repaired. Re-inspection required
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods Traction sheave liner is deteriorated and needs replacing
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements Replace broken shackle springs for suspension ropes in machine room. 6/15/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.1 General Maintenance Requirements Documentation Replace 2 broken shackle springs on hoisting cable shackles. 6/15/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods A rope saver is worn on drive sheave and shall be replaced.
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x Fire service needs to be tested. Re-inspection required 7/8/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x The testing has not been completed on the elevator at this time. Emergency power operation shall be performed before the inspection is completed. 12/5/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Need to test elevator for operation on emergency power. Re-inspection required
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A copy of the current operating certificate shall be displayed in the machine room