MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 Maintenance, Repair and Replacements
|
No
|
No
|
Replace broken shackle springs for suspension ropes in machine room.
|
6/15/2021
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.2.1 General Maintenance Requirements Documentation
|
No
|
No
|
Replace 2 broken shackle springs on hoisting cable shackles.
|
6/15/2021
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6 General Maintenance Methods
|
No
|
No
|
A rope saver is worn on drive sheave and shall be replaced.
|
9/22/2025
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6 General Maintenance Methods
|
No
|
No
|
Traction sheave liner is deteriorated and needs replacing
|
9/22/2025
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
No
|
No
|
Current operating certificate shall be displayed in the machine room
|
9/22/2025
|
|
MO Minimum : Elevators
|
(S) - Fire Service
|
211.7 Firefighters Operations/Signage
|
No
|
No
|
Call Cancel button shall be labeled.
|
9/22/2025
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
No
|
No
|
A copy of the current operating certificate shall be displayed in the machine room
|
9/22/2025
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
No
|
No
|
Current Operating Certificate shall be displayed in the machine room
|
10/10/2025
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
Yes
|
No
|
Test not complete. Need to test hoistway doors, gate switch, slack tape switch, hoist ropes, car top equipment, pit equipment, soft set safety, no load car and counterweight buffer test, governor switch, escape hatch, top and bottom final and directional limits, runby, pit switches
|
|
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
Yes
|
No
|
Phone in elevator cab does not work on battery backup or normal power, needs repaired. Re-inspection required
|
8/21/2025
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
Yes
|
No
|
Need to test elevator for operation on emergency power. Re-inspection required
|
8/21/2025
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
Yes
|
No
|
Emergency Power needs to be tested - Test not completed
|
9/22/2025
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
Yes
|
No
|
The testing has not been completed on the elevator at this time. Emergency power operation shall be performed before the inspection is completed.
|
12/5/2023
|
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection)
|
Yes
|
No
|
Fire service needs to be tested. Re-inspection required
|
7/8/2022
|