Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A copy of the current operating certificate shall be displayed in the machine room
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No The testing has not been completed on the elevator at this time. Emergency power operation shall be performed before the inspection is completed. 12/6/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Test elevator for operation on emergency power. Re-inspection required
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) Yes No Test phase 1 & 2 fire service 1/5/2022
MO Minimum : Elevators (I) - Pits (I)2 No No Test car buffer at rated speed, rated load
MO Minimum : Elevators (I) - Pits (I)2 No No Test counterweight buffer at rated speed
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) Yes No The emergency car lighting is not operational, likely indicating that the back-up power device (battery) has failed. The fixture shall be repaired to operate. Reinspection required. 12/6/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) Yes No When testing the audible signaling device (alarm bell) with the 110V disconnect in the machine room in the “off” position, the device failed to sound, indicating that the back-up power device (battery) has failed. Repair for proper operation. Reinspection required. 12/6/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods No No Traveling cable support (kellum) is broken at 22nd floor, needs to be replaced
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) Yes No Elevator cab phone does not work on battery backup, needs repaired. Re-inspection required