Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts No No Down final limit switch roller is damaged and needs to be replaced 8/18/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods No No Clean debris from compensation rope sheave groove in elevator pit 8/18/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods No No Replace sheave liner on traction machine sheave due to wear. 8/18/2026
MO Minimum : Elevators (I) - Pits (I)2 No No Test car buffer at rated speed, rated load 8/18/2026
MO Minimum : Elevators (I) - Pits (I)2 No No Test counterweight buffer at rated speed 8/18/2026
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A copy of the current operating certificate shall be displayed in the machine room 8/18/2026
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Test elevator operation on emergency power. Re-inspection required 8/18/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) Yes No Elevator cab emergency lights do not work, needs repaired. Re-inspection required 8/18/2026
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) Yes No Test phase 1 & 2 fire service 1/5/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) Yes No The emergency car lighting is not operational, likely indicating that the back-up power device (battery) has failed. The fixture shall be repaired to operate. Reinspection required. 12/5/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) Yes No When testing the audible signaling device (alarm bell) with the 110V disconnect in the machine room in the “off” position, the device failed to sound, indicating that the back-up power device (battery) has failed. Repair for proper operation. Reinspection required. 12/5/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No The testing has not been completed on the elevator at this time. Emergency power operation shall be performed before the inspection is completed. 12/5/2023
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) Yes No Elevator cab phone does not work on battery backup. Re-inspection required 8/18/2026
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) Yes No 1 of the 2 door open buttons in the elevator cab does not work on Phase II fire service. Re-inspection required 8/18/2026
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) Yes No Right COP door close button shall function during FEO Phase II.
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)12 (Re- Inspection) Yes Yes Governor rope shall be replaced due to kink and breaks.
MO Minimum : Elevators (M) - Car Safeties and Speed Governors (M)1 Yes Yes Full Load safety slide did not meet the minimum slide distance.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements Yes No Emergency power was tested. Power did not transfer and selector did not operate and shall be repaired. (60 days reinspect)