MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 Maintenance, Repair and Replacements
|
Yes
|
No
|
Emergency power was tested. Power did not transfer and selector did not operate and shall be repaired. (60 days reinspect)
|
|
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection)
|
Yes
|
No
|
Phase 2 fires service does not operate and shall be corrected.
|
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6 General Maintenance Methods
|
No
|
No
|
Sheave liners are deteriorated and shall be replaced.
|
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6 General Maintenance Methods
|
No
|
No
|
Roller guides bearings on top of car, left side, are deteriorated and shall be replaced
|
|
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection)
|
Yes
|
No
|
Test phase I & II fire service, Re-inspection required in 30 days
|
1/6/2022
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
Yes
|
No
|
The testing has not been completed on the elevator at this time. The elevator was out of service at the time of inspection and a machine room inspection could only be performed.
|
8/17/2026
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)4
|
No
|
No
|
Test car buffer at rated speed, rated load, Re-inspection required in 30 days
|
8/17/2026
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)4
|
No
|
No
|
Test counterweight buffer at rated speed, Re-inspection required in 30 days
|
8/17/2026
|