Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (I) - Pits (I)4 No No Test car buffer at rated speed, rated load, Re-inspection required in 30 days 8/17/2026
MO Minimum : Elevators (I) - Pits (I)4 No No Test counterweight buffer at rated speed, Re-inspection required in 30 days 8/17/2026
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) Yes No Test phase I & II fire service, Re-inspection required in 30 days 1/6/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No The testing has not been completed on the elevator at this time. The elevator was out of service at the time of inspection and a machine room inspection could only be performed. 8/17/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements Yes No Emergency power was tested. Power did not transfer and selector did not operate and shall be repaired. (60 days reinspect)
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods No No Sheave liners are deteriorated and shall be replaced.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods No No Roller guides bearings on top of car, left side, are deteriorated and shall be replaced
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) Yes No Phase 2 fires service does not operate and shall be corrected.