Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (I) - Pits (I)4 No No Test car buffer at rated speed, rated load, Re-inspection required in 30 days 8/17/2026
MO Minimum : Elevators (I) - Pits (I)4 No No Test counterweight buffer at rated speed, Re-inspection required in 30 days 8/17/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods No No Sheave liners are deteriorated and shall be replaced.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods No No Roller guides bearings on top of car, left side, are deteriorated and shall be replaced
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) Yes No Phase 2 fires service does not operate and shall be corrected.
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) Yes No Test phase I & II fire service, Re-inspection required in 30 days 1/6/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No The testing has not been completed on the elevator at this time. The elevator was out of service at the time of inspection and a machine room inspection could only be performed. 8/17/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements Yes No Emergency power was tested. Power did not transfer and selector did not operate and shall be repaired. (60 days reinspect)