Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (D) - Brakes (D)2 x x Test machine brake with 125% of rated load, Re-inspection required in 30 days 1/7/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x The emergency car lighting is not operational, likely indicating that the back-up power device (battery) has failed. The fixture shall be repaired to operate. Reinspection required.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x When testing the audible signaling device (alarm bell) with the 110V disconnect in the machine room in the “off” position, the device failed to sound, indicating that the back-up power device (battery) has failed. Repair for proper operation. Reinspection required.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods Safety rod pull up bushings have deteriorated and shall be replaced.
MO Minimum : Elevators (I) - Pits (I)2 Test car buffer at rated speed, rated load. Re-inspection required in 30 days
MO Minimum : Elevators (I) - Pits (I)2 Test counterweight buffer at rated speed. Re-inspection required in 30 days
MO Minimum : Elevators (M) - Car Safeties and Speed Governors (M)1 x x Test car safety with rated load, rated speed. Re-inspection required in 30 days 1/7/2022
MO Minimum : Elevators (S) - Fire Service (S)1 x x Test phase I & II fire service, Re-inspection required in 30 days 1/7/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x The testing has not been completed on the elevator at this time. Emergency power operation shall be performed before the inspection is completed.