MO Minimum : Elevators
|
(D) - Brakes
|
(D)2
|
x
|
x
|
Test machine brake with 125% of rated load, Re-inspection required in 30 days
|
1/7/2022
|
MO Minimum : Elevators
|
(M) - Car Safeties and Speed Governors
|
(M)1
|
x
|
x
|
Test car safety with rated load, rated speed. Re-inspection required in 30 days
|
1/7/2022
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)2
|
|
|
Test car buffer at rated speed, rated load. Re-inspection required in 30 days
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)2
|
|
|
Test counterweight buffer at rated speed. Re-inspection required in 30 days
|
|
MO Minimum : Elevators
|
(S) - Fire Service
|
(S)1
|
x
|
x
|
Test phase I & II fire service, Re-inspection required in 30 days
|
1/7/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection)
|
x
|
|
The emergency car lighting is not operational, likely indicating that the back-up power device (battery) has failed. The fixture shall be repaired to operate. Reinspection required.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection)
|
x
|
|
When testing the audible signaling device (alarm bell) with the 110V disconnect in the machine room in the “off” position, the device failed to sound, indicating that the back-up power device (battery) has failed. Repair for proper operation. Reinspection required.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6 General Maintenance Methods
|
|
|
Safety rod pull up bushings have deteriorated and shall be replaced.
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
The testing has not been completed on the elevator at this time. Emergency power operation shall be performed before the inspection is completed.
|
|