Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (I) - Pits (I)2 No No Test car buffer at rated speed, rated load. Re-inspection required in 30 days
MO Minimum : Elevators (I) - Pits (I)2 No No Test counterweight buffer at rated speed. Re-inspection required in 30 days
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods No No Safety rod pull up bushings have deteriorated and shall be replaced.
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No The testing has not been completed on the elevator at this time. Emergency power operation shall be performed before the inspection is completed.
MO Minimum : Elevators (D) - Brakes (D)2 Yes Yes Test machine brake with 125% of rated load, Re-inspection required in 30 days 1/7/2022
MO Minimum : Elevators (M) - Car Safeties and Speed Governors (M)1 Yes Yes Test car safety with rated load, rated speed. Re-inspection required in 30 days 1/7/2022
MO Minimum : Elevators (S) - Fire Service (S)1 Yes Yes Test phase I & II fire service, Re-inspection required in 30 days 1/7/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) Yes No The emergency car lighting is not operational, likely indicating that the back-up power device (battery) has failed. The fixture shall be repaired to operate. Reinspection required.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) Yes No When testing the audible signaling device (alarm bell) with the 110V disconnect in the machine room in the “off” position, the device failed to sound, indicating that the back-up power device (battery) has failed. Repair for proper operation. Reinspection required.