Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Test incomplete, need to perform 125% brake test. Re-inspection required 1/24/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Test incomplete, need to perform full load buffer test for car & counterweight. Re-inspection required 1/24/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Test incomplete, need to perform full load safety set. Re-inspection required 1/24/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Test incomplete, need to test spin governor. Re-inspection required 1/24/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Need to test elevator for operation on emergency power. Re-inspection required
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency bell is not working. Re-inspection required 1/24/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency light and alarm bell do not work. 7/21/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Door Systems 8.6.4.13 (Re-Inspection) x Replace missing fire tabs on the lobby floor door 12/7/2023
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) Repair inoperative pit light
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) Need to repair pit lighting
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A copy of the current operating certificate shall be displayed in the machine room
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x Emergency power operation needs to be tested 12/7/2023
conversion conversion n/a Remove standing water from the elevator pit. If water continues to accumulate in the elevator pit, a permanent means to remove the water shall be provided. 5/7/2019