MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - Door Systems 8.6.4.13 (Re-Inspection)
|
x
|
|
The car door electric contacts shall be adjusted to prevent operation of the driving machine when the clear open space between the leading edge of the door and the nearest face of the jamb exceeds 2 inches.
|
12/4/2020
|
MO Minimum : Elevators
|
(L) - Wire Ropes-Hoisting, Governor and Tiller
|
(L)1(A)
|
|
|
A metal data tag shall be securely attached to the governor rope fastenings bearing the wire rope data required.
|
3/16/2022
|
MO Minimum : Elevators
|
(L) - Wire Ropes-Hoisting, Governor and Tiller
|
(L)1(A)
|
|
|
A metal data tag shall be securely attached to one of the suspension wire rope fastenings bearing the wire rope data required.
|
3/16/2022
|
A17.1-1996 : Elevators
|
1.17 - Standby power operation
|
211.2
|
x
|
|
The emergency/standby power shall be tested.
|
7/2/2024
|
A17.1-1996 : Elevators
|
1.17 - Standby power operation
|
1001.2(a)(17)
|
x
|
|
Emergency power shall be tested.
|
11/21/2019
|
A17.1-1996 : Elevators
|
1.17 - Standby power operation
|
1001.2(a)(17)
|
x
|
|
Emergency power shall be tested per A17.1
|
1/29/2020
|
A17.1-1996 : Elevators
|
1.17 - Standby power operation
|
1001.2(a)(17)
|
x
|
|
Emergency power shall be tested per A17.1
|
3/19/2020
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Fire service operation shall be tested as required.
|
7/2/2024
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Firefighters operation category 1 test shall be performed.
|
12/29/2020
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Firefighters operation category 1 test shall be performed.
|
12/4/2020
|
A17.1-1996 : Elevators
|
2.17 - Drive machine brake
|
1001.2(b)(15)
|
x
|
x
|
The machine brake failed to hold 125% capacity. Unit Red-Tagged and locked out of service.
|
11/21/2019
|
A17.1-1996 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
Code compliant maintenance records (MCP) shall be available and kept on-site.
|
3/16/2022
|
A17.1-1996 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
Code compliant maintenance records (MCP) shall be available and kept on-site.
|
3/16/2022
|
A17.1-1996 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
Code compliant maintenance records (MCP) shall be available and kept on-site.
|
3/16/2022
|
A17.1-1996 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
Code compliant maintenance records (MCP) shall be available and kept on-site.
|
3/16/2022
|
A17.1-1996 : Elevators
|
3.23 - Suspension rope
|
1001.2(c)(29)
|
x
|
|
Hoist ropes and rouged and approaching minimum diameter and shall be replaced.
|
3/19/2020
|
A17.1-1996 : Elevators
|
3.23 - Suspension rope
|
1001.2(c)(29)
|
x
|
|
Hoist ropes and rouged and approaching minimum diameter and shall be replaced.
|
5/8/2020
|
A17.1-1996 : Elevators
|
3.23 - Suspension rope
|
1001.2(c)(29)
|
x
|
|
Hoist ropes and rouged and approaching minimum diameter and shall be replaced.
|
1/29/2020
|
A17.1-1996 : Elevators
|
3.23 - Suspension rope
|
1001.2(c)(29)
|
x
|
|
Hoist ropes and rouged and approaching minimum diameter and shall be replaced.
|
11/21/2019
|
A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
106.1e Illumination of Pits
|
|
|
The pit light shall be operational.
|
3/16/2022
|
A17.1-1996 : Elevators
|
5.2 - Bottom clearance, runby, and minimum refuge space
|
1001.2(e)(2)
|
x
|
|
The counterweight runby shall not be less than 6". Provide code compliant counterweight runby.
|
1/4/2022
|
A17.1-1996 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
1206.7
|
|
|
Fire service emergency operation shall be tested monthly and documented. Records shall be kept on-site.
|
3/16/2022
|
A17.1-1996 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
1206.7
|
|
|
Fire service emergency operation shall be tested monthly and documented. Records shall be kept on-site.
|
3/16/2022
|
A17.1-1996 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
211.2-211.8
|
x
|
x
|
Phase 1 & 2 fire service shall be tested at part of the Category 5 safety test.
|
11/21/2019
|
A17.1-1996 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
1206.7
|
x
|
x
|
Fire service emergency operation shall be tested monthly and documented. Records shall be kept on-site.
|
11/21/2019
|
A17.1-1996 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
1206.7
|
|
|
Fire service emergency operation shall be tested monthly and documented. Records shall be kept on-site.
|
3/16/2022
|
A17.1-1996 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
211.2-211.8
|
x
|
x
|
Phase 1 & 2 fire service shall be tested at part of the Category 5 safety test.
|
1/29/2020
|
A17.1-1996 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
1206.7
|
x
|
x
|
Fire service emergency operation shall be tested monthly and documented. Records shall be kept on-site.
|
1/29/2020
|
conversion
|
conversion
|
conversion - reinspect
|
x
|
|
Replace the worn guide roller on top of car.
|
10/8/2019
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Display the current state operating certificate.
|
3/16/2022
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Display the current state operating certificate.
|
3/16/2022
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Display the current state operating certificate.
|
3/16/2022
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Obtain and display a current state operating certificate.
|
3/16/2022
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO state operating certificate shall be posted in the elevator machine room in a noncombustible frame with a clear protective vision plate over it.
|
3/16/2022
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
3/16/2022
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
|