Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
conversion conversion conversion - reinspect Yes No Replace the worn guide roller on top of car. 10/8/2019
A17.1-1996 : Elevators 1.17 - Standby power operation 1001.2(a)(17) Yes No Emergency power shall be tested. 11/21/2019
A17.1-1996 : Elevators 2.17 - Drive machine brake 1001.2(b)(15) Yes Yes The machine brake failed to hold 125% capacity. Unit Red-Tagged and locked out of service. 11/21/2019
A17.1-1996 : Elevators 3.23 - Suspension rope 1001.2(c)(29) Yes No Hoist ropes and rouged and approaching minimum diameter and shall be replaced. 11/21/2019
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1206.7 Yes Yes Fire service emergency operation shall be tested monthly and documented. Records shall be kept on-site. 11/21/2019
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 211.2-211.8 Yes Yes Phase 1 & 2 fire service shall be tested at part of the Category 5 safety test. 11/21/2019
A17.1-1996 : Elevators 1.17 - Standby power operation 1001.2(a)(17) Yes No Emergency power shall be tested per A17.1 1/29/2020
A17.1-1996 : Elevators 3.23 - Suspension rope 1001.2(c)(29) Yes No Hoist ropes and rouged and approaching minimum diameter and shall be replaced. 1/29/2020
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1206.7 Yes Yes Fire service emergency operation shall be tested monthly and documented. Records shall be kept on-site. 1/29/2020
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 211.2-211.8 Yes Yes Phase 1 & 2 fire service shall be tested at part of the Category 5 safety test. 1/29/2020
A17.1-1996 : Elevators 1.17 - Standby power operation 1001.2(a)(17) Yes No Emergency power shall be tested per A17.1 3/19/2020
A17.1-1996 : Elevators 3.23 - Suspension rope 1001.2(c)(29) Yes No Hoist ropes and rouged and approaching minimum diameter and shall be replaced. 3/19/2020
A17.1-1996 : Elevators 3.23 - Suspension rope 1001.2(c)(29) Yes No Hoist ropes and rouged and approaching minimum diameter and shall be replaced. 5/8/2020
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Firefighters operation category 1 test shall be performed. 12/4/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Door Systems 8.6.4.13 (Re-Inspection) Yes No The car door electric contacts shall be adjusted to prevent operation of the driving machine when the clear open space between the leading edge of the door and the nearest face of the jamb exceeds 2 inches. 12/4/2020
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Firefighters operation category 1 test shall be performed. 12/29/2020
A17.1-1996 : Elevators 5.2 - Bottom clearance, runby, and minimum refuge space 1001.2(e)(2) Yes No The counterweight runby shall not be less than 6". Provide code compliant counterweight runby. 1/4/2022
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)1(A) No No A metal data tag shall be securely attached to the governor rope fastenings bearing the wire rope data required. 3/16/2022
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)1(A) No No A metal data tag shall be securely attached to one of the suspension wire rope fastenings bearing the wire rope data required. 3/16/2022
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits No No The pit light shall be operational. 3/16/2022
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1206.7 No No Fire service emergency operation shall be tested monthly and documented. Records shall be kept on-site. 3/16/2022
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1206.7 No No Fire service emergency operation shall be tested monthly and documented. Records shall be kept on-site. 3/16/2022
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1206.7 No No Fire service emergency operation shall be tested monthly and documented. Records shall be kept on-site. 3/16/2022
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Obtain and display a current state operating certificate. 3/16/2022
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Display the current state operating certificate. 3/16/2022
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Display the current state operating certificate. 3/16/2022
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Display the current state operating certificate. 3/16/2022
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 3/16/2022
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current MO state operating certificate shall be posted in the elevator machine room in a noncombustible frame with a clear protective vision plate over it. 3/16/2022
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 No No Code compliant maintenance records (MCP) shall be available and kept on-site. 3/16/2022
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 No No Code compliant maintenance records (MCP) shall be available and kept on-site. 3/16/2022
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 No No Code compliant maintenance records (MCP) shall be available and kept on-site. 3/16/2022
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 No No Code compliant maintenance records (MCP) shall be available and kept on-site. 3/16/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Fire service operation shall be tested as required. 7/2/2024
A17.1-1996 : Elevators 1.17 - Standby power operation 211.2 Yes No The emergency/standby power shall be tested. 7/2/2024
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 8/18/2025