Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.2(d) On-Site Documentation (Written Procedures for Evacuation and Cleaning) A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Evacuation procedures are missing.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. MCP shall be kept in machine room, not on car top.
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be obtained and displayed in the elevator machine room.
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be obtained and displayed in the elevator machine room.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements Clean the car top. 3/17/2022
MO Minimum : Elevators (I) - Pits (I)1 Clean the pit. 3/17/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.7.2 Periodic Test Record (Test Tags) Current test tags shall be installed on governor, safeties (releasing carrier), buffers, etc.
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator.
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Emergency/standby power operation of the elevator shall be operational. 12/29/2021
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Fire service shall be tested. 12/29/2021
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Fire service shall be tested.
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)1(A) Install hoist rope data tags.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records Provide a code compliant MCP including onsite documents. (This item is for notification purposes for future violation in 2022) 3/17/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements Provide numbering on car top. 3/17/2022
conversion conversion conversion - reinspect x Re-install the 6th floor hoistway dust cover. 5/31/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements Re-install the 6th floor hoistway dust cover. (Violation not cleared from previous annual inspection) 3/17/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements Replace missing bottom door guide at the 5th floor hoistway door. 3/17/2022
MO Minimum : Elevators (A) - Hoistways (A)16 Replace missing interlock covers in the hoistway. There are exposed live wires.
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)12 (Re- Inspection) x Replace the governor rope. Violation repaired on 9/21/2020 and scheduled for re-inspection on 10/5/2020 10/5/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13 - Door systems x The car door restrictor vane is missing on the 2nd floor hoistway door. 3/2/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates The car numbering on the crosshead is incorrect. The proper elevator number shall be displayed on the crosshead.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.9 Cleaning of Top of Cars The car top shall be cleaned.
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x The emergency bell shall work. 5/14/2020
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting The emergency lights shall work. 3/17/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x The in car emergency bell shall be operational on main and auxiliary power. (2nd Notice)
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x The in car emergency bell shall be operational. (2nd Notice) 3/2/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x The in car emergency light and bell shall be operational. 3/2/2023