Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be obtained and displayed in the elevator machine room.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.2(d) On-Site Documentation (Written Procedures for Evacuation and Cleaning) A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Evacuation procedures are missing.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates The car numbering on the crosshead is not correct. The correct elevator number shall be displayed on the crosshead.
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)1(A) Provide hoist rope data tags.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Door Systems 8.6.4.13 (Re-Inspection) x Rear car door restrictor shall work.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.7.2 Periodic Test Record (Test Tags) Current test tags shall be installed on governor, safeties (releasing carriers), buffers, etc.
MO Minimum : Elevators (I) - Pits (I)1 The pit shall be kept clean and free of dirt, oil, and debris. Remove excess debris.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records Required documentation and MCP shall be kept in equipment room including wiring diagrams, oil log & fire service recorded monthly.
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate State operating certificate is not in the machine room.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates The car numbering on the crosshead is not correct. The correct elevator number shall be displayed on the crosshead. This unit is #11 but cartop numbers on cross-head and operator are painted as #9.
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Fire service shall be tested.
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator
conversion conversion conversion - reinspect x Replace missing gib on 1st floor hoistway door. 5/31/2019
conversion conversion conversion - reinspect x Phase 2 fire service call cancel shall work. 5/31/2019
MO Minimum : Elevators (S) - Fire Service (S)1 x Phase 2 fire service call cancel shall work. (Violation not cleared from previous annual inspection) 7/30/2020
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x In car emergency bell shall work. 7/30/2020
MO Minimum : Elevators (S) - Fire Service (S)1 x x The call cancel feature does not work on Phase 2 fire service. Violation corrected on 9/21/2020 and scheduled for re-inspection on 10/5/2020. 10/5/2020
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Fire service Phase 1 & 2 shall be tested. 12/29/2021
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. 12/29/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements Replace missing fire stop on hoistway door at 1st floor. 3/17/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements Replace missing gib on 1st floor hoistway door. (Violation not cleared from previous annual inspection) 3/17/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements Clean the car top. 3/17/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements Provide numbering on car top. 3/17/2022
MO Minimum : Elevators (I) - Pits (I)1 Clean the pit. 3/17/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements Provide a code data plate on the controller. 3/17/2022
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting In car emergency lighting shall work. 3/17/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.2(d) On-Site Documentation (Written Procedures for Evacuation and Cleaning) Written evacuation procedures for elevators by authorized persons and emergency personnel shall be available on-site. 3/18/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 3/18/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements The wire-rope retaining clips shall be properly installed. At least two wire-rope retaining clips shall be provided to attach the termination side to the load-carrying side of the rope (see Figure 2.20.9.5). The first clip shall be placed a maximum of 4 times the rope diameter above the socket, and the second clip shall be located within 8 times the rope diameter above the first clip. 3/18/2022
MO Minimum : Elevators (H) - Machine Rooms (H)8 The disconnect located in the machine space shall be provided with a sign to identify the location of the supply side overcurrent protective device. 3/18/2022
MO Minimum : Elevators (I) - Pits (I)1 Clean the pit of dirt and debris. 3/18/2022
MO Minimum : Elevators (I) - Pits (I)3 Counterweight guards shall extend from a point not more than twelve inches (12") above the pit floor to a point not less than seven feet (7') above the pit floor. 3/18/2022