Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. 12/29/2021
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Fire service Phase 1 & 2 shall be tested. 12/29/2021
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Fire service shall be tested. 6/18/2025
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator 6/18/2025
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) Yes No In car emergency bell shall work. 7/30/2020
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting No No In car emergency lighting shall work. 3/17/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Door Systems 8.6.4.13 (Re-Inspection) Yes No Rear car door restrictor shall work. 6/18/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements No No Provide a code data plate on the controller. 3/17/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements No No Replace missing fire stop on hoistway door at 1st floor. 3/17/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements No No Replace missing gib on 1st floor hoistway door. (Violation not cleared from previous annual inspection) 3/17/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements No No Clean the car top. 3/17/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements No No Provide numbering on car top. 3/17/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements No No The wire-rope retaining clips shall be properly installed. At least two wire-rope retaining clips shall be provided to attach the termination side to the load-carrying side of the rope (see Figure 2.20.9.5). The first clip shall be placed a maximum of 4 times the rope diameter above the socket, and the second clip shall be located within 8 times the rope diameter above the first clip. 3/18/2022
MO Minimum : Elevators (H) - Machine Rooms (H)8 No No The disconnect located in the machine space shall be provided with a sign to identify the location of the supply side overcurrent protective device. 3/18/2022
MO Minimum : Elevators (I) - Pits (I)1 No No Clean the pit of dirt and debris. 3/18/2022
MO Minimum : Elevators (I) - Pits (I)1 No No Clean the pit. 3/17/2022
MO Minimum : Elevators (I) - Pits (I)1 No No The pit shall be kept clean and free of dirt, oil, and debris. Remove excess debris.
MO Minimum : Elevators (I) - Pits (I)3 No No Counterweight guards shall extend from a point not more than twelve inches (12") above the pit floor to a point not less than seven feet (7') above the pit floor. 3/18/2022
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)1(A) No No Provide hoist rope data tags.
MO Minimum : Elevators (S) - Fire Service (S)1 Yes No Phase 2 fire service call cancel shall work. (Violation not cleared from previous annual inspection) 7/30/2020
MO Minimum : Elevators (S) - Fire Service (S)1 Yes Yes The call cancel feature does not work on Phase 2 fire service. Violation corrected on 9/21/2020 and scheduled for re-inspection on 10/5/2020. 10/5/2020
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current MO State operating certificate shall be obtained and displayed in the elevator machine room.
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No State operating certificate is not in the machine room.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.2(d) On-Site Documentation (Written Procedures for Evacuation and Cleaning) No No A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Evacuation procedures are missing.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.2(d) On-Site Documentation (Written Procedures for Evacuation and Cleaning) No No Written evacuation procedures for elevators by authorized persons and emergency personnel shall be available on-site. 3/18/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records No No A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 3/18/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records No No Required documentation and MCP shall be kept in equipment room including wiring diagrams, oil log & fire service recorded monthly.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates No No The car numbering on the crosshead is not correct. The correct elevator number shall be displayed on the crosshead. This unit is #11 but cartop numbers on cross-head and operator are painted as #9.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates No No The car numbering on the crosshead is not correct. The correct elevator number shall be displayed on the crosshead.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.7.2 Periodic Test Record (Test Tags) No No Current test tags shall be installed on governor, safeties (releasing carriers), buffers, etc.
conversion conversion conversion - reinspect Yes No Replace missing gib on 1st floor hoistway door. 5/31/2019
conversion conversion conversion - reinspect Yes No Phase 2 fire service call cancel shall work. 5/31/2019