conversion
|
conversion
|
conversion - reinspect
|
x
|
|
The fireman's emergency service phase I and II operations was tested and the following deficiency was noted:The proximity door protection device is not rendered inoperative when phase I operation is initiated. Reinspection is required.
|
12/5/2018
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
|
|
The emergency car lighting is not operational, likely indicating that the back-up power device (battery) has failed. The fixture shall be repaired to operate.
|
11/19/2019
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
|
|
When testing the audible signaling device (alarm bell) with the 110V disconnect in the machine room in the “off” position, the device failed to sound, indicating that the back-up power device (battery) has failed. Repair for proper operation.
|
11/19/2019
|
conversion
|
conversion
|
n/a
|
|
|
The belts on the hydraulic pump motor are mismatched and worn unevenly. Replace belts for a smooth operation of pump to motor.
|
5/26/2020
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
The current state operating certificate needs to be posted in the machine room in a non-combustible frame.
|
5/26/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting)
|
x
|
|
The elevator ADA telephone inside the elevator is not working properly. Check and repair the phone line of this phone for proper operation and passenger safety
|
4/29/2021
|