Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) Yes No Alarm bell back up was dead. 11/20/2019
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)3 No No There was no emergency exit on the elevator cab. This does not meet A17.3 as required by St. Louis County 5/26/2020
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting No No Emergency Light back up was dead 5/26/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements No No The car top inspection light/fixture did not operate. Repair fixture/light for proper operation and illumination for maintenance/emergency personnel 5/26/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements No No There were no car door restrictors. This does not meet A17.3 as required for St. Louis County 5/26/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) Yes No The elevator ADA telephone inside the elevator is not working properly. Check and repair this phone for proper operation and passenger safety. Reinspection required. 3/1/2022
A17.1-2016 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 No No Replace the fire extinguisher with new or have current extinguisher serviced. Extinguisher last serviced 2023
conversion conversion n/a No No The car top inspection light is damaged and doesn?t operate. Repair fixture for proper operation. 5/26/2020
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No The current state operating certificate needs to be posted in the machine room in a non-combustible frame 5/26/2020