conversion
|
conversion
|
conversion - reinspect
|
x
|
|
The fireman's emergency service phase I and II operations was tested and the following deficiency was noted:The proximity door protection device is not rendered inoperative when phase I operation is initiated. Reinspection is required.
|
12/6/2018
|
MO Minimum : Elevators
|
(S) - Fire Service
|
(S)1
|
x
|
|
Safe edge not over-ridden on FES Phase I
|
11/20/2019
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)3
|
|
|
No emergency exit on car top. Car cannot comply with A17.3 as required for St. Louis County
|
5/26/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection)
|
x
|
|
No car door restrictor. Car cannot comply with A17.3 as required for St. Louis County
|
11/20/2019
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Car 110 volt battery back up was dead
|
11/20/2019
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)8 Car Lighting
|
|
|
Emergency Light/alarm bell back up was dead
|
5/26/2020
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
The current state operating certificate needs to be posted in the machine room in a non-combustible frame.
|
5/26/2020
|