Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Car 110 volt battery back up was dead 11/20/2019
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting Emergency Light/alarm bell back up was dead 5/26/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) x No car door restrictor. Car cannot comply with A17.3 as required for St. Louis County 11/20/2019
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)3 No emergency exit on car top. Car cannot comply with A17.3 as required for St. Louis County 5/26/2020
MO Minimum : Elevators (S) - Fire Service (S)1 x Safe edge not over-ridden on FES Phase I 11/20/2019
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate The current state operating certificate needs to be posted in the machine room in a non-combustible frame. 5/26/2020
conversion conversion conversion - reinspect x The fireman's emergency service phase I and II operations was tested and the following deficiency was noted:The proximity door protection device is not rendered inoperative when phase I operation is initiated. Reinspection is required. 12/6/2018