Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Emergency phone not working, alarm bell ok on battery power. 10/17/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.2 Oil Leakage Collection Scavenger pump in pit. Remove, and connect pit jugs to each jack. 11/16/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency phone not working. Needs battery. Phone works on 110 1/18/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.2 Oil Leakage Collection Scavenger pump in pit. 11/16/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) x Car door restrictor not working 3/28/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.2 Oil Leakage Collection Scavenger pump being used in pit 3/3/2022
MO Minimum : Elevators (H) - Machine Rooms (H)2 Machine room door needs to be self-locking 3/3/2022
MO Minimum : Elevators (I) - Pits (I)1 Pit needs old leak debris cleaned 11/16/2022
A17.1-1996 : Elevators 2.8 - Pipes, wiring, and ducts 102.1 Install metal cover on 4x4 gangboxes and resistor box mounted on side of controller. 11/3/2020
A17.1-2016 : Elevators 5.11 - Plunger and Cylinder 8.6.5.5 Remove scavenger pump from pit. Cylinder drain line needs to be ran to pit container with no more than 5 gallon capacity. 11/3/2020
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.11.1 Firefighters’ Emergency Operation Documentation Test and log firefighter operation monthly 11/3/2020