Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 2.4 - Machine space 101.1a Repair holes in machine wall below disconnect to maintain fire rating 6/1/2023
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Alarm bell inoperable, and shall be repaired or replaced. 4/25/2025
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) x Auxiliary lighting inoperable, and shall be repaired or replaced. 4/25/2025
A17.1-2016 : Elevators 5.15 - Overspeed Valve 8.6.5.16.5 OSV is overdue for testing. Perform required testing, seal & tag within 90 days. 6/1/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) A copy of the MCP shall be kept in the machine room for each elevator 6/1/2023
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current State Elevator Certificate. 6/1/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Provide existing battery backup lowering unit to work properly. 5/8/2023