MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4.1(a) On-Site Maintenance Records (MCP Records)
|
|
|
A copy of the MCP shall be kept in the machine room for each elevator
|
6/1/2023
|
A17.1-2016 : Elevators
|
5.15 - Overspeed Valve
|
8.6.5.16.5
|
|
|
OSV is overdue for testing. Perform required testing, seal & tag within 90 days.
|
6/1/2023
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Post current State Elevator Certificate.
|
6/1/2023
|
A17.1-1996 : Elevators
|
2.4 - Machine space
|
101.1a
|
|
|
Repair holes in machine wall below disconnect to maintain fire rating
|
6/1/2023
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Alarm bell inoperable, and shall be repaired or replaced.
|
4/25/2025
|
A17.1-1996 : Elevators
|
1.5 - Car lighting and receptacles
|
204.7a (3)(a) Standby Illumination in the car. (Re-Inspection)
|
x
|
|
Auxiliary lighting inoperable, and shall be repaired or replaced.
|
4/25/2025
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Battery back up did not work upon reinspection. Must be retested
|
5/12/2023
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Provide existing battery backup lowering unit to work properly.
|
5/8/2023
|