MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)8 Car Lighting
|
|
|
open egg crate ceiling in elevator cab, provide covers for the light tubes
|
11/11/2021
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
No active telephone
|
11/22/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 Maintenance, Repair and Replacements
|
|
|
replace worn out roller guides
|
8/3/2020
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
x
|
|
No lockable machine room door
|
11/22/2022
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)5 (Machine Room Lighting)
|
x
|
|
Insufficient machine room lighting
|
11/22/2022
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)7
|
x
|
x
|
No main line disconnect
|
11/22/2022
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
pit has water/oil mixture several inches deep - sump pump not working
|
11/11/2021
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)6 (Pit Lighting)
|
|
|
pit light switch broke, turned on but will not turn off
|
11/11/2021
|
MO Minimum : Elevators
|
(S) - Fire Service
|
(S)1
|
x
|
x
|
No smoke detectors or heat detector
|
11/22/2022
|
A17.1-2016 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
2.8.2
|
|
|
NEC - label location of the feeder panel on the disconnect
|
7/23/2024
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
post current copy of the state operating certificate in the machine space
|